Makeup Air

Pressure, not CFM

A chimney doesn't feel CFM. It feels pressure. Safety limits are set in Pascals, code sizes fireplace air in square inches, and building tightness is rated by blower door. None of them start with the CFM on a fireplace calculation, and makeup air shouldn't either.

How much does your fireplace need? Run the numbers

Three kinds of air

Makeup air is the one exhaust forgets.

AirJob
Ventilation airDilutes indoor pollutants for the occupants
Makeup airReplaces what exhaust appliances remove
Combustion airFeeds fuel-burning appliances

Pair an ERV or HRV for ventilation air with VMASS for makeup air. They do different jobs.

The cracked window

Everyone has seen makeup air work.

Crack a window an inch and a smoky, backdrafting fireplace starts drafting, a trick installers have used for decades.

That inch of window moves far less air than most people expect, because the house already supplies most of the air through its own envelope, and makeup air only has to close the gap.

OpeningAt −5 PaAt −10 PaAt −20 Pa
36" window cracked 1" (36 sq in)~85 CFM~120 CFM~170 CFM
Code-maximum fireplace outside air (55 sq in)~130 CFM~185 CFM~260 CFM

Calculated for a sharp-edged opening. A real duct and grille moves less.

Two diagrams. Window shut: exhaust pulls the room negative and smoke rolls into the room. Window cracked 1 inch: outdoor air replaces what the chimney pulls and the fireplace drafts.

The code agrees

Code sizes fireplace air in square inches, not hundreds of CFM.

IRC R1006 expects a wood-burning fireplace's outside air supply to deliver all of its combustion air through an opening of 6 to 55 square inches, and at the −7 Pa limit for wood-burning appliances, 55 square inches moves only ~150 CFM.

The same section waives the outside air supply when the room is mechanically ventilated and controlled so the indoor pressure is neutral or positive, which means the code measures the result in pressure.

So why size makeup air to the fireplace's full exhaust?

Safety is in Pascals

Every combustion safety limit is set in Pascals.

Combustion safety testing never asks how many CFM a house supplies, only how negative the room gets, with a limit for each kind of appliance.

If safety is judged in Pascals, makeup air should be designed in Pascals too.

Appliance in the spaceMaximum depressurization
Atmospheric water heater−2 Pa
Atmospheric water heater and furnace−3 Pa
Category I or fan-assisted furnace−5 Pa
Wood-burning appliances−7 Pa
Sealed combustion, forced draft−25 Pa

DOE Standard Work Specifications, combustion appliance zone depressurization limits.

Pressure scale from 0 to −25 Pa: atmospheric water heater at −2 Pa, water heater plus furnace at −3 Pa, Category I furnace at −5 Pa, wood-burning appliances at −7 Pa, sealed combustion at −25 Pa. More negative means more risk of spillage.

Same CFM, different pressure

The building decides what a CFM is worth.

How much pressure a CFM imbalance creates depends on how tight the building is, so the same 100 CFM that barely registers in an older house can push a Passive House past the spill point of an open fireplace.

Matching CFM in to CFM out ignores the building, while designing to pressure includes it.

How code made houses this tight: How Houses Got Tight

Example house100 CFM short400 CFM short
Older home, 5 ACH500.4 Pa3.5 Pa
Today's energy code, 3 ACH500.9 Pa7.7 Pa
High-performance, 1 ACH504.9 Pa42 Pa
Passive House, 0.6 ACH5011 Pa92 Pa

Calculated for a 3,000 sq ft house with 9 ft ceilings, envelope flow exponent 0.65. ACH50: blower-door air changes per hour at 50 Pa. Red: past the 3 to 4 Pa where an open fireplace on natural draft can begin to spill.

How much exhaust does it take to spill a fireplace?

Bar chart of exhaust needed to spill an open fireplace in the same 3,000 sq ft house: older home about 400 CFM, today's energy code about 240 CFM, high-performance about 80 CFM, Passive House about 50 CFM. A typical bath fan moves 50 to 100 CFM.

Fire vs opening

The fire needs very little air. It's the opening that pulls on the envelope.

It takes ~10 cubic feet of air to burn 1,000 BTU of any fuel, so a 60,000 BTU/hr open gas fire needs ~10 CFM to burn, and a vigorous wood fire only slightly more.

Most of what leaves through an open fireplace is dilution air: room air swept up the chimney to keep smoke and fumes in the firebox. It drives the large number in any fireplace calculation, and it is the part a draft inducer controls.

The gas code sizes combustion air the same way, with NFPA 54 calling for one square inch of opening to outdoors per 3,000 BTU/hr, or ~33 square inches for a 100,000 BTU/hr appliance.

FireplaceWhat the fire needsWhat leaves the room
Open gas, with draft inducer~10 CFM per 60,000 BTU/hrMostly dilution air through the face, controlled by the draft inducer
Open wood, with draft inducerSmall, similar to gasThe most dilution air, highest at a cold start
Sealed glass-front gas, for comparisonDrawn from outdoorsNo room air
Fireplace cross-section: a thick arrow of dilution air sweeps across the face and up the chimney past the draft inducer, while a thin arrow of combustion air, about 10 CFM per 60,000 BTU/hr, feeds the fire. Most of what leaves the room is dilution air, not combustion air.

Two numbers, two jobs

Size the draft inducer for the cold start. Size makeup air for the house.

A fireplace calculation sizes the draft inducer with the ASHRAE face velocity method: enough pull across the opening to keep smoke in at a cold start, the worst moment. That number is for sizing a draft inducer, not for sizing makeup air.

Published makeup air tables are built the same way: opening size × a design velocity. What they leave out is the air the building already supplies.

Makeup air answers a different question: once the fire is established, how much of the air leaving the room does the building not already supply?

Makeup air needed = operating exhaust − what the envelope supplies at the pressure you allow

42 in. gas opening, ~315 CFM of room airAllow −2 PaAllow −5 PaAllow −7 Pa
3,000 sq ft, 3 ACH50~150 CFM~15 CFM0
6,000 sq ft, 3 ACH50000
3,000 sq ft, 1 ACH50~260 CFM~215 CFM~190 CFM

Calculated with the same envelope assumptions as above. Tight houses with large fireplaces can need two VMASS units; most need less makeup air than the fireplace calculation suggests. With a draft inducer on the fireplace, the allowable pressure is set by the other appliances in the house, not the fireplace.

Dial the draft inducer down

Turn the draft inducer down. The makeup air problem shrinks.

The draft inducer decides how much room air leaves through the fireplace, and when it is sized for a cold start, it can pull far more than the fire needs once the flue is warm.

Every CFM the draft inducer doesn't pull is a CFM the house doesn't have to replace. X-VENTISO controllers are commissioned at the lowest speed that holds the draft, and Meridian goes further, modulating continuously to only what the moment needs.

The same turn of the dial also makes the system quieter and sends less heated room air up the chimney.

Fireplace exhaustMakeup air neededVMASS units
~555 CFM (XV250 at full speed)~255 CFM1
~450 CFM (42 in. opening, wood)~150 CFM1
~315 CFM (42 in. opening, gas)~15 CFM1, near its 25 CFM baseline
300 CFM0Not needed for the fireplace

Example: 3,000 sq ft house, 3 ACH50, room allowed to reach −5 Pa, where the envelope supplies ~300 CFM. On a 400°F flue, flue gas is ~40% thinner than room air: the XV250's 900 CFM rating at full speed is ~555 CFM of room air. Calculated with the envelope assumptions above.

The cost of too much

Dumping in air has a price.

  • Moisture

    Pushes air into the walls

    Supply 600 CFM when exhaust is pulling less, and a code-tight house goes ~14 Pa positive, driving warm, moist indoor air into the building envelope.

  • Energy

    Heats air nobody needed

    Warming 600 CFM of 20°F outdoor air to room temperature takes ~9.5 kW.

  • Comfort

    Drafts and doors

    Over-supply shows up as whistling doors, drafts, and rooms that never feel settled.

Control it like temperature

Nobody runs a furnace flat out and hopes.

If heating is controlled to a temperature, then makeup air needs to be controlled to a pressure.

Two gauges side by side: heating, controlled to a temperature of 70°F, equals makeup air, controlled to a pressure of 0 Pa.

A passive opening only lets air in once the room is already negative, because the pressure difference is what pulls the air through, while a fan that senses the room delivers air before the chimney loses.

VMASS controls the zone to neutral against outdoor pressure, within 0.02 in. w.c., and supplies only the air the zone needs.

Follow the room, not the hood

Matching the hood's speed is still matching CFM.

Most powered makeup air on the market answers the exhaust fan, not the room. A sensor on the hood's power reads whether it is running high, medium, or low, and the makeup air fan steps to a matching speed set on commissioning day.

It is CFM matching, automated. The house gets balanced to pressure once, at startup, and never checked again. After that the system knows the hood's speed and nothing else.

It cannot see a fireplace or a dryer, because they are not on the hood's circuit. It cannot see how tight the house is, a second exhaust running at the same time, wind, or the stack effect on a January night. It cannot tell whether the room is negative at all.

Where code asks for makeup air matched to a kitchen hood, VMASS is interlocked with the hood and sized to its rating. But a hood is rarely the only thing pulling on the house, and VMASS answers all of it.

A hood-tracking system knows what the hood is doing. VMASS knows what the room is doing.

QuestionDamper that opens with the hoodFan that tracks the hood's speedVMASS
Answers toHood on or offHood speed: high, medium, lowThe room
MeasuresNothingThe hood's power drawZone pressure against outdoors, continuously
SuppliesWhatever the negative room pulls inA preset share of the hood's CFMOnly what holds the zone neutral, 25 to 400 CFM
Sees a fireplace, dryer, or second exhaustNoNoYes, anything that pulls the zone
Knows how tight the house isNoOnce, at commissioningEvery second
Tempers the airNoHeats the full matched airflowHeats only the air the zone needs
Two floor plans. Follows the hood: a sensor on the range hood's power drives the makeup air unit, and the fireplace and dryer are not seen. Follows the room: a room pressure sensor sees everything that pulls on the room, including the hood, fireplace, dryer, wind, and stack effect.

Five questions

Five questions to ask about any makeup air system.

A lower box price is easy to see. These are the costs that show up after it.

  1. 01

    What does it measure?

    The hood's speed, or the pressure in the room? Only one of them is what the chimney feels.

  2. 02

    What circuit does the heater need?

    Heating 600 CFM of 20°F air to room temperature takes ~9.5 kW: a 240 V circuit of ~50 A. VMASS plugs into 120 V outlets.

  3. 03

    What size duct?

    Moving hood-matched airflow quietly takes 10 to 12 inch duct through the framing. VMASS runs on 6 inch.

  4. 04

    Who commissions it?

    Calibrating to the hood's speeds and balancing the house takes a technician and a gauge. VMASS is factory-sealed, with nothing to calibrate.

  5. 05

    What does it cost to run?

    Every time the hood goes to high, a hood-matched system heats air the house may never have needed.

Price the whole install, not the box.

Send us the plans and we will size VMASS for the house, with the circuit, duct, and heat it actually needs.

Submit plans

The math

The math behind every number on this page.

Every figure above comes from a handful of standard relationships. Here they are, with the example worked through, so you can run them for your own project.

StepRelationshipWorked example
Building leakage coefficientC = CFM50 ÷ 50n, where CFM50 = ACH50 × volume ÷ 603,000 sq ft × 9 ft = 27,000 ft³ at 3 ACH50: CFM50 = 1,350, C ≈ 106
Air the envelope suppliesQ = C × ΔPn, with n ≈ 0.65 and ΔP in PaAt −5 Pa: 106 × 50.65 ≈ 300 CFM
Pressure from an imbalanceΔP = (Q ÷ C)1/n400 CFM short: (400 ÷ 106)1.54 ≈ 7.7 Pa
Makeup air neededQmakeup = Qexhaust − C × ΔPallowedn42 in. gas opening, 315 CFM, at −5 Pa: 315 − 300 ≈ 15 CFM
Flow through an openingQ = Cd × A × 4,005 × √ΔP, with A in ft², ΔP in in. w.c., Cd ≈ 0.636 sq in (0.25 ft²) at −5 Pa (0.020 in. w.c.): ≈ 85 CFM
Air leaving the roomQ = opening area × face velocity (wood ≈ 0.8 ft/s, ASHRAE cold start; gas ≈ 0.56 ft/s)42-1/2 × 31-5/8 in. opening (~9.3 sq ft): gas 9.3 × 0.56 × 60 ≈ 315 CFM; wood ≈ 450 CFM
Air the fire burns~10 ft³ of air per 1,000 BTU60,000 BTU/hr: ≈ 10 CFM
Heat to temper outdoor airkW = 1.08 × CFM × ΔT ÷ 3,412600 CFM from 20°F to 70°F: ≈ 9.5 kW

Envelope relationship per the ASHRAE Handbook of Fundamentals, infiltration chapter, with a typical flow exponent of 0.65. 1 in. w.c. = 249 Pa. Results are estimates for comparison; we size each project from its own plans.

Makeup Air Field GuidePDF, 4 pages (PDF, opens in a new tab)

Common questions

What engineers ask us.

Q.01Does the house's own leakage really count?
Yes. Every house leaks, and that leakage supplies part of what exhaust pulls out. The tighter the house, the less it supplies, which is why a high-performance home can reach the spill point with a bath fan running while an older home barely notices 400 CFM. Makeup air closes the gap the envelope leaves.
Q.02What exhaust number should we design to?
A fireplace calculation sizes the draft inducer for a cold start, the hardest few minutes of the fire. Once the flue is warm, the draft inducer runs at its commissioned speed, and Meridian modulates lower still. The draft inducer you select, and the speed it is set to, decide what the house actually has to replace.
Q.03With a draft inducer on the fireplace, what sets the safe pressure?
The other combustion appliances in the house. An open fireplace on natural draft can begin to spill at 3 to 4 Pa. A draft inducer sized for the fireplace keeps the chimney in draft well past that, and Meridian pulls harder as the room goes negative. How far depends on the opening, the flue, and the speed, which is what we size for. The limit that matters becomes the next most sensitive appliance in the zone: a water heater, a furnace, or nothing at all in an all-electric or sealed-combustion home. NFPA 211 makes this the test: a mechanical draft system must not cause other combustion equipment to spill, verified with the other exhaust equipment running (NFPA 211-2019, 4.1.2.2 to 4.1.2.4).
Q.04Why not a passive opening?
A passive opening only lets air in once the room is already negative, because the pressure difference is what pulls air through it. It brings in outdoor air at outdoor temperature, and it cannot tell a calm night from a windy one. A powered unit that senses the room supplies air before the room drops.
Q.05What about kitchen hoods?
Kitchen hoods over 400 CFM get their own makeup air, sized to the hood: code asks for makeup air approximately equal to the exhaust rate, starting automatically with the hood. VMASS is interlocked with the hood and sized one unit per 400 CFM of hood rating. Because it controls to pressure, it also answers the fireplace, the dryer, and everything else pulling on the same zone.
Q.06When does a project need two units?
When the combined demand in a zone is more than one unit supplies: typically a large open fireplace in a very tight house, or a large hood where code asks for makeup air matched to its rating. One unit covers most fireplace zones. Send us the plans and we will tell you which yours is.

Local amendments vary. Confirm requirements with the authority having jurisdiction.

We size it

Send us the plans.

Size makeup air to pressure, not to a nameplate.

Design the zone, not the appliances. We size the draft inducer and the makeup air for the zone together, from your plans, for the house and the climate. One design, one call.