Meridian Series

Self-modulating draft control for gas-fired appliances

Meridian measures the flue and the space it serves, then modulates the draft inducer continuously on that pressure differential to provide only the draft the appliance needs. Quiet, fully automatic, and no commissioning required.

X-VENTISO Meridian draft controller.
  1. 01 · MeasureThe flue and the space it serves
  2. 02 · CompareThe differential between them is draft
  3. 03 · ModulateXV-FLUX adjusts continuously
  4. 04 · ProveDraft proven before the appliance lights
  5. 05 · ReportBACnet or Modbus, set up at our factory

Modulation

Draft, measured against the space it serves.

Most draft controls hold a fixed stack setpoint. Meridian references two pressures, the flue and the space the appliance serves, and controls the difference between them. That differential is draft itself.

When exhaust equipment pulls the space negative, the differential drops and Meridian responds by pulling harder. When conditions ease, it backs off. The draft inducer only works as hard as the moment requires.

No speed to set and nothing to dial in at commissioning.

Meridian measures pressure in the flue and in the space the appliance serves, and modulates the draft inducer on the difference between them.

Quiet

Quiet because it only works as hard as it has to.

A fixed-speed draft inducer runs at the speed its worst day needs, every hour it runs. Meridian runs at the speed this moment needs. When the weather is calm and nothing is pulling the space negative, that can be well below full speed.

Two dials. A fixed-speed draft inducer runs near full speed every hour. Meridian runs at what the moment needs, moving through a range as conditions change.

Sound falls sharply as speed comes down. At reduced speed, XV Series draft inducers tested 23 to 34 dB quieter than full speed (38 V test point). To the ear, every 10 dB drop sounds about half as loud.

Quiet is not a setting. It is what happens when the draft inducer runs only as fast as the moment needs.

Tested sound data

Sequence of operation

Meridian proves draft before the appliance lights.

  1. 01

    Call for heat

    The appliance's own control initiates the call. Meridian never fires the appliance.

  2. 02

    Draft inducer starts

    The draft inducer starts as soon as the call comes in.

  3. 03

    Damper proves open

    Where the flue has a damper, Meridian confirms it is open before going further. If it does not prove open, the appliance does not light. X-VENTISO gas dampers fail closed if power is lost, and the appliance cannot light until the damper proves open again.

  4. 04

    Positive draft established

    XV-FLUX drives the flue-to-space differential to setpoint and proves positive draft.

  5. 05

    Appliance released

    Only with draft proven does the interlock release the gas appliance module to light.

  6. 06

    Continuous modulation

    Meridian holds the setpoint as conditions change: wind, stack temperature, and exhaust equipment pulling the space negative.

  7. 07

    Call ends, flue purged

    When the call ends, the draft inducer runs a 15-second post-purge to clear the flue, shown on Meridian's display, then shuts down.

  8. 08

    If draft is lost

    If draft cannot be held at any point, Meridian shows an alarm on its display, shuts the gas appliance down through the interlock, and runs the post-purge to clear the flue.

In the box

Everything code asks for, in the box.

IncludedMeridianMeridian DUO
Plugs into a standard 120V outletIncludedIncluded
Factory-wired, plug-in Molex connectionsIncludedIncluded
Stack probe and pressure tubingIncludedIncluded(one set per flue)
Damper proving, where a damper is usedIncludedIncluded(each flue)
Draft proven before ignitionIncludedIncluded
Gas interlock (NFPA 54)IncludedIncluded
AlarmVisual, on displayVisual, on display
Service disconnect at draft inducerIncludedIncluded
BACnet or Modbus, set up at our factoryIncludedIncluded

Meridian is for gas-fired appliances. For solid fuel, specify Controlled Power WBC, which carries the audible and visual alarm NFPA 211 requires. Requirement-by-requirement detail on the Code Compliance page.

X-VENTISO XV-MERD-DUO controller with factory-wired leads.
XV-MERD-DUO.
New

Meridian DUO: Two Flues, One Controller.

Meridian DUO serves two flues from one factory-sealed enclosure, and modulates each one on its own, against the space it serves.

What ships

  • Controller

    Meridian Controller

    Factory-sealed, with factory-wired Molex leads to the draft inducer and damper. Plugs into a standard 120V outlet.

  • Flue

    Stack Probe and Tubing

    Reads pressure in the flue. One set per flue on Meridian DUO.

  • Space

    Room Sensor and Tubing

    Reads pressure in the space the appliance serves. One per flue on Meridian DUO.

  • Gas

    Gas Interlock Lead

    4-pin Molex black lead to the appliance gas control. The same hookup as GBC, so installers already know it.

  • Docs

    Installation Manual

    Included in the box. Also available under Downloads.

Installer supplies: the XV Series draft inducer and a 120V outlet. The gas interlock lead connects at the appliance gas control.

BAS integration

BACnet and Modbus, integrated before it ships.

Choose BACnet or Modbus when you order, and it is set up at our factory before Meridian ships. For BACnet, XV-BACnet INTF is integrated at the factory, so the BAS connects over BACnet/IP with an Ethernet cable. No one opens the controller on site. Meridian reports status, alarm, draft pressure, draft inducer speed, and damper position, and accepts an enable / disable command from the building automation system.

Automation can turn Meridian on and off. It never fires the appliance. The gas interlock stays with Meridian.

BACnet PICS and Modbus register map (protocol variants, object list, registers): available on request. Call 800.642.2920.

PointAccessDescription
Run statusReadOn / off
Draft pressureReadFlue-to-space differential, in. w.c.
Alarm statusReadActive / clear, including loss of draft
Draft inducer speedReadSpeed, percent
Damper positionReadOpen / closed
System enableWriteEnable or disable the Meridian system. Does not fire the appliance.

Compatibility

One system, factory matched.

Specifications

Meridian specifications.

SpecificationMeridianMeridian DUO
Model numberXV-MERD-CTRLXV-MERD-DUO
FuelGas-fired appliancesGas-fired appliances
Flues served12, controlled independently
Pressure transducers12, one per flue
ReferenceFlue and served spaceEach flue to its own served space
ModulationXV-FLUX, continuousXV-FLUX, continuous, per flue
CommissioningNone required. Nothing to dial in.None required. Nothing to dial in.
Draft provingPressure, stack probe and tubing includedPressure, stack probe and tubing included
Gas interlockInterlocked with the appliance gas controlInterlocked with the appliance gas control
AlarmVisual, on displayVisual, on display
BASBACnet/IP (XV-BACnet INTF, factory-integrated, Ethernet) or Modbus RTU, set up at the factoryBACnet/IP (XV-BACnet INTF, factory-integrated, Ethernet) or Modbus RTU, set up at the factory
PowerPlugs into a standard 120V outlet (NEMA 5-15 plug)Plugs into a standard 120V outlet (NEMA 5-15 plug)
Electrical rating120 VAC, 50/60 Hz, 6.0 A120 VAC, 50/60 Hz, 12.0 A
Low-voltage circuitsClass 2, from the controller’s internal power supplyClass 2, from the controller’s internal power supply
EnclosureNEMA 1 (indoor). Sealed at the factory; no field-serviceable partsNEMA 1 (indoor). Sealed at the factory; no field-serviceable parts
ListingsUL 508 Industrial Control Panels · UL/ULC 378 Draft Equipment. ETL Listed, Intertek control no. 4007025UL 508 Industrial Control Panels · UL/ULC 378 Draft Equipment. ETL Listed, Intertek control no. 4007025

Controllers are factory-sealed. Opening the enclosure voids the warranty.